Tests for Electric Cables under Fire Conditions - Circuit Integrity - Part 31: Procedures and Requirements for Fire with Shock - Cables of Rated Voltage uo to and Inculding 0,6/1 kV
Introduction: IEC 60331 consists of the following parts under the general title: Tests for electric cables under fire conditions – Circuit integrity: Part 11: Apparatus – Fire alone at a flame temperature of at least 750 °C Part 12: Apparatus – Fire with shock at a temperature of at least 830 °C NOTE 1 Further parts are under consideration (e.g. for fire with water spray). Part 21: Procedures and requirements – Cables of rated voltage up to and including 0,6/1,0 kV Part 23: Procedures and requirements – Electric data cables Part 25: Procedures and requirements – Optical fibre cables NOTE 2 Parts 21, 23 and 25 relate to fire-only conditions. Part 31: Procedures and requirements for fire with shock – Cables of rated voltage up to and including 0,6/1,0 kV IEC 60331-31 introduces procedures and requirements for use where cables are tested under conditions of mechanical shock as well as fire. It requires that the apparatus introduced as IEC 60331-12 be used, thereby meeting an increasing demand for more comprehensive testing of circuit integrity cables.
Scope: This part of IEC 60331 specifies the test procedure and gives the performance requirement, including a recommended flame application time, for cables of rated voltage up to and including 0,6/1,0 kV required to maintain circuit integrity when subjected to fire and mechanical shock under specified conditions. It is intended for use when testing cables of greater than 20 mm overall diameter. It describes the means of sample preparation, the continuity checking arrangements, the electrical testing procedure, the method of burning the cables and the method of shock production, and gives requirements for evaluating test results. This part of IEC 60331 is applicable to low-voltage power cables, and control cables with a rated voltage. NOTE Although the scope is restricted to cables with rated voltage up to and including 0,6/1,0 kV, the procedure may be used, with the agreement of the manufacturer and the purchaser, for cables with rated voltage up to and including 3,3 kV, provided that suitable fuses are used.