Polymeric HV insulators for indoor and outdoor use - General definitions, test methods and acceptance criteria
Introduction: Polymeric insulators consist either of one insulating material (resin insulators) or two or several insulating materials (composite insulators). The insulating materials are generally cross-linked organic materials synthesised from carbon or silicon chemistry and form the insulating body. Insulating materials can be composed from organic materials containing various inorganic and organic ingredients, such as fillers and extenders. End fittings are often used at the ends of the insulating body to transmit mechanical loads. Despite these common features, the materials used and the construction details employed by manufacturers might differ significantly. The tests given in this document are those which are, in general, common to a majority of insulator designs and materials, whatever their final application. Considering the increasing applications of polymeric insulators, the scope of this document specifies technical requirements for solid core, hollow core and resin insulators used in AC and DC systems, in indoor and outdoor, in applications of HV overhead lines and substations to ensure proper insulator performance under normal operating conditions. The technical requirements have been regrouped in this document to avoid repetition of the relevant product standards and drift between procedures as the various product standards are drafted or revised. The majority of these tests have been grouped together as "Design tests", to be performed only once for insulators of the same
Scope: This International Standard is applicable to polymeric insulators for AC systems with a nominal voltage greater than 1 000 V (frequency less than 100 Hz) and DC systems with a nominal voltage greater than 1 500 V whose insulating body consists of one or various organic materials. Polymeric insulators covered by this document are intended for use both on HV overhead lines and in substations, in both indoor and outdoor applications. They include composite insulators with solid and hollow core and resin insulators. Hybrid insulators with ceramic core and polymeric housing are also included, while coated insulators (e.g. with RTV silicone rubber coatings) are not included in this standard. Electrical tests described in this document are done under AC voltage and are in general applicable to insulators to be used in DC systems too. Tests under DC voltage are intended to reflect up-to-date knowledge and experience. NOTE Only polymeric housing materials of hybrid insulators are specified in this document. Tests for core materials and the interfaces between housing and core of hybrid insulators are not included. The object of this document is to define the common terms used for polymeric insulators; to prescribe common test methods for design tests on polymeric insulators; to prescribe acceptance or failure criteria, if applicable; These tests, criteria and recommendations are intended to ensure a satisfactory lifetime under normal operating and environmental conditions (see Clause 5). This document includes design tests intended to reject materials or designs which are inadequate under normal operating and environmental conditions. This document defines test methods and acceptance criteria. The applicable tests are given in the relevant product standard.
Contents:
- FOREWORD
- INTRODUCTION
- Scope