Residual current operated circuit-breakers for household and similar use – Part 3-1: Particular requirements for devices with screwless-type terminals for external copper conductors
Introduction: This document is part of the series described in the outline document IEC 62873-1.
Scope: This part of IEC 62873 applies to RCDs equipped with screwless terminals, for current not exceeding 20 A primarily suitable for connecting unprepared (see 3.5) copper conductors of cross-section up to 4 mm2. This part of IEC 62873 cannot be used alone but it is intended to be applied together with an RCD product standard (IEC 61008-1 or IEC 61009-1) if an RCD is equipped with screwless terminals. NOTE In AT, CZ, DK, NL, NO, PO, PT and CH, the upper limit of current for use of screwless terminals is 16 A. This document applies to devices equipped with screwless-type terminals for current not exceeding 40 A, primarily suitable for connecting unprepared copper conductors of cross-section up to 10 mm2. This document cannot be used alone but is intended to be applied together with the applicable product standard in which it is referred to. NOTE 1 In CZ, DK, NL, PO and CH, the upper limit of current for use of screwless-type terminals is 16 A. NOTE 2 In JP, the upper limit of current for use of screwless-type terminals is 30 A. NOTE 3 The manufacturer can declare in its documentation specific conditions permitting the use of prepared conductors. In this document, screwless-type terminals are referred to as terminals, and copper conductors are referred to as conductors.
Contents:
- FOREWORD
- INTRODUCTION
- Scope