This standard describes the composition, performance requirements, construction practices and workmanship, design, and methods of testing thermosetting fiberglass-reinforced plastic (FRP) tanks for storing water and other liquids in water supply service. It is limited to atmospheric-pressure, vented, cylindrical and spherical tanks installed aboveground or underground, with service temperatures not exceeding 180°F (82°C) aboveground and 150°F (66°C) underground. Service limits for environmental exposure and structural loads are established from tests of laminates representative of the materials and fabrication methods used, and the standard sets the quality requirements for commercially available contact-molded and filament-wound tanks.