ANSI/AWWA C213 describes the material and application requirements for fusion-bonded epoxy coatings and linings on steel water pipe, special sections, welded joints, connections, fittings, and appurtenances installed underground or underwater. Fusion-bonded epoxies are heat-activated, chemically cured systems applied as a dry powder that melts, flows, and crosslinks on the prepared steel surface. The minimum diameter for epoxy lining that can be inspected and repaired by entry is 24 in. (600 mm); smaller pipe may be included where it can be electrically inspected internally and the work complies with the standard. Coating performance is based on potable-water service temperatures.