Float operated valves-Specification for compact type float operated valves for WC flushing cisterns (including floats)
Publishing information: This part of BS 1212 is published by BSI Standards Limited, under licence from The British Standards Institution, and came into effect on 29 February 2016. It was prepared by Technical Committee B/504, Water Supply. A list of organizations represented on this committee can be obtained on request to its secretary. Supersession This part of BS 1212 supersedes BS 1212-4:1991, which is withdrawn. Relationship with other publications This part of BS 1212 is part of a series that contains the following parts: Part 1: Specification for piston type float operated valves (copper alloy body) (excluding floats); Part 2: Specification for diaphragm type float operated valves (copper alloy body) (excluding floats); Part 3: Specification for diaphragm type float operated valves (plastics bodied) for cold water services only (excluding floats); Part 4: Specification for compact type float operated valves for WC flushing cisterns (including floats).
Information about this document: This is a full revision of the standard, and introduces the following principal changes: updated throughout to allow for the state of the art currently used in the field e.g. push fit connectors; introduction of a specific delayed action inlet test.
Presentational conventions: The provisions of this standard are presented in roman (i.e. upright) type. Its requirements are expressed in sentences in which the principal auxiliary verb is “shall”. Commentary, explanation and general informative material is presented in smaller italic type, and does not constitute a normative element. Requirements in this standard are drafted in accordance with Rules for the structure and drafting of UK standards, subclause J.1.1, which states, “Requirements should be expressed using wording such as: ‘When tested as described in Annex A, the product shall ...’”. This means that only those products that are capable of passing the specified test will be deemed to conform to this standard. Terms of measurement are expressed in metric units except for the designations of pipe threads which are retained in imperial units in accordance with BS 2779.
Scope: This part of BS 1212 specifies requirements for materials, connecting dimensions, overall size limitations and performance of compact float operated valves, incorporating a float designed for use at operating pressures of between 0.1 bar and 10 bar 1) and intended for use in WC flushing cisterns.
Contents:
- Foreword
- Scope
- Annexes
- Annex A (normative) Distortion test for backnuts and inlet shanks
- Annex B (normative) High pressure shut-off test
- Annex C (normative) Low pressure shut-off test
- Annex D (normative) Dynamic pressure test
- Annex E (normative) Vacuum test
- Annex F (normative) Flow test
- Annex G (normative) Endurance test
- Annex H (normative) Delayed action inlet valve test
- Bibliography