Oil-filled electrical equipment – Sampling of free gases and analysis of free and dissolved gases in mineral oils and other insulating liquids – Guidance
Introduction: Gases can be formed in oil-filled electrical equipment due to natural ageing but also, to a much greater extent, as a result of faults. Operation with a fault can seriously damage the equipment, and it is valuable to be able to detect the fault at an early stage of development. Where a fault is not severe, the gases formed will normally dissolve in the oil, with a small proportion eventually diffusing from the liquid into any gas phase above it. Extracting dissolved gas from a sample of the oil and determining the amount and composition of this gas is a means of detecting such faults, and the type and severity of any fault can often be inferred from the composition of the gas and the rate at which it is formed. In the case of a sufficiently severe fault, free gas will pass through the oil and collect in the gas- collecting (Buchholz) relay if fitted; if necessary, this gas may be analysed to assist in determining the type of fault that has generated it. The composition of gases within the bubbles changes as they move through the oil towards the gas-collecting relay. This can be put to good use, as information on the rate of gas production can often be inferred by comparing the composition of the free gases collected with the concentrations remaining dissolved in the liquid. The interpretation of the gas analyses is the subject of IEC 60599. These techniques are valuable at all stages in the life of oil-filled equipment. During acceptance tests on transformers in the factory,
Scope: This document deals with the techniques for sampling free gases from gas-collecting relays from power transformers. Three methods of sampling free gases are described. The techniques for sampling oil from oil-filled equipment such as power and instrument transformers, reactors, bushings, oil-filled cables and oil-filled tank-type capacitors are no longer covered by this document, but are instead described in IEC 60475:2022, 4.2. Before analysing the gases dissolved in oil, they are first extracted from the oil. Three basic methods are described, one using extraction by vacuum (Toepler and partial degassing), another by displacement of the dissolved gases by bubbling the carrier gas through the oil sample (stripping) and the last one by partition of gases between the oil sample and a small volume of the carrier gas (headspace). The gases are analysed quantitatively after extraction by gas chromatography; a method of analysis is described. Free gases from gas-collecting relays are analysed without preliminary treatment. The preferred method for ensuring the performance of the gas extraction and analysis equipment, considered together as a single system, is to degas samples of oil prepared in the laboratory and containing known concentrations of gases ("gas-in-oil standards") and quantitatively analyse the gases extracted. Two methods of preparing gas-in-oil standards are described. For daily calibration checks of the chromatograph, it is convenient to use a standard gas mixture containing a suitable known amount of each of the gas components to be in a similar ratio to the common ratios of the gases extracted from transformer oils. The techniques described take account, on the one hand, of the problems peculiar to analyses associated with acceptance testing in the factory, where gas contents of oil are generally very low and, on the other hand, of the problems imposed by monitoring equipment in the field, where transport of samples can be by un-pressurized air freight and where considerable differences in ambient temperature can exist between the plant and the examining laboratory.
Contents:
- FOREWORD
- INTRODUCTION
- Scope