IEC 61620-1998 PDF

IEC 61620-1998 PDF

Insulating Liquids - Determination of the Dielectric Dissipation Factor by Measurement of the Conductance and Capacitance - Test Method

$100.88 $201.76 -50%
Product Code: IEC 61620
Stock In Stock
Edition: 1.0
Published: 11/1998
Number of Pages: 52
File Size: 1 file, 199 Bytes

Available Options

Product Description

Insulating Liquids - Determination of the Dielectric Dissipation Factor by Measurement of the Conductance and Capacitance - Test Method

Introduction: The conductivity σ is a characteristic of a liquid only if it is measured at thermodynamic equilibrium. To fulfil this requirement high electric stress and/or prolonged voltage application is to be avoided, this is not the case in IEC 60247 for the d.c. resistivity measurement (electric stress up to 250 Vmm–1, conventional arbitrary time of electrification 1 min). There is a simple relationship between the dielectric dissipation factor tan δ, the conductivity σ and the permittivity ε of the liquid with no (or negligible) dipolar losses, which is the case of most liquids for electrotechnical applications: tan = εω where ω = 2 πf and f is the frequency of the voltage. Therefore, the measurement of either tan δ or σ gives the same information on the conduction properties of the liquid. In fact, very often in practice, there are large discrepancies between the resistivity calculated from the measurement of tan δ with conventional apparatus and the d.c. resistivity measured following the recommendation of IEC 60247. New devices for the measurement of the conductivity σ at thermodynamic equilibrium are currently available. They are able to measure easily and with precision very low values of σ. The capabilities of this new equipment allow measurements of σ of unused insulating liquids even at room temperature.

Scope: This International Standard describes a method for the simultaneous measurement of conductance G and capacitance C enabling the calculation of the dielectric dissipation factor tan δ of insulating liquids. The proposed method applies both to unused insulating liquids and insulating liquids in service in transformers and in other electrical equipment. The standard is no substitute for IEC 60247; rather it complements it insofar as it is particularly suited to highly insulating liquids and it recommends a method of measurement for these liquids. This method allows values of the dielectric dissipation factor as low as 10–6 at power frequency to be determined with certainty. Moreover, the range of measurements of tan δ lies between 10–6 and 1 and can be extended up to 200 in particular conditions.

Contents:

  • FOREWORD
  • INTRODUCTION
  • Scope
  • 10 Test report
  • 11 Precision

Be the first to write a review for this product.