Insulators for overhead lines – Composite line post insulators for A.C. systems with a nominal voltage greater than 1 000 V – Definitions, test methods and acceptance criteria
Introduction: Composite line post insulators consist of a cylindrical solid insulating core, bearing the mechanical load, protected by a polymeric housing, the loads being transmitted to the core by metal fittings. Despite these common features, the materials used and the construction details employed by different manufacturers may be different. Some tests have been grouped together as "design tests", to be performed only once on insulators which satisfy the same design conditions. All the design tests defined in IEC 62217 are applied for composite line post insulators; additional specific mechanical tests are given in this standard. As far as practical, the influence of time on the electrical and mechanical properties of the components (core material, housing, interfaces, etc.) and of the complete composite insulators has been considered in specifying the design tests to ensure a satisfactory life-time under normally known stress conditions of transmission lines. Composite insulators are used in both a.c. and d.c. applications. In spite of this fact a specific tracking and erosion test procedure for d.c. applications as a design test has not yet been defined and accepted. The 1 000 h a.c. tracking and erosion test of IEC 62217 is used to establish a minimum requirement for the tracking resistance of the housing material. The approach for mechanical testing under bending loads used in this standard is based on the work of CIGRE [1]1. This approach uses the concept of a damage limit which i
Scope: This International Standard applies to composite line post insulators consisting of a load- bearing cylindrical insulating solid core consisting of fibres – usually glass – in a resin-based matrix, a housing (outside the insulating core) made of polymeric material and end fittings permanently attached to the insulating core. Composite line post insulators covered by this standard are subjected to cantilever, tensile and compressive loads, when supporting the line conductors. They are intended for use on a.c. overhead lines with a rated voltage greater than 1 000 V and a frequency not greater than 100 Hz. The object of this standard is to define the terms used, to prescribe test methods, to prescribe acceptance or failure criteria. This standard does not include requirements dealing with the choice of insulators for specific operating conditions.
Contents:
- FOREWORD
- INTRODUCTION
- Scope
- 10 Design tests
- 10.1 General
- 10.2 Test specimens for IEC 62217
- 10.2.1 Tests on interfaces and connections of end fittings
- 10.2.2 Tracking and erosion test
- 10.2.3 Tests on core material
- 10.3 Product specific pre-stressing for IEC 62217 tests on interfaces and
- 10.3.1 Thermal-mechanical pre-stressing
- 10.4 Assembled core load tests
- 10.4.1 Test for the verification of the maximum design cantilever load
- 10.4.2 Tensile load test
- 11 Type tests
- 11.1 Electrical tests
- 11.1.1 Vertical mounting arrangement
- 11.1.2 Horizontal mounting arrangement
- 11.2 Mechanical tests
- 11.2.1 Cantilever failing load test
- 12 Sample tests
- 12.1 General rules
- 12.2 Verification of dimensions (E1 + E2)
- 12.3 Galvanizing test (E1 + E2)
- 12.4 Verification of the SCL (E1)
- 12.4.1 Test procedure
- 12.4.2 Acceptance criteria
- 12.5 Re-testing procedure
- 13 Routine tests
- 13.1 Tensile load test