Communication networks and systems for power utility automation – Part 9-3: Precision time protocol profile for power utility automation
Introduction: General This part of IEC 61850 specifies a precision time protocol (PTP) profile of IEC 61588:2009 ¦ IEEE Std 1588-2008 applicable to power utility automation, which allows compliance with the highest synchronization classes of IEC 61850-5 and IEC 61869-9. This part of IEC 61850 applies Layer 2 communication according to IEC 61588:2009 ¦ IEEE Std 1588-2008, Annex F, and uses peer-to-peer delay measurement according to the default profile of IEC 61588:2009 ¦ IEEE Std 1588-2008, Annex J.4, with restricted range of values. When clocks are singly attached, this profile is a subset of IEC 61588:2009 ¦ IEEE Std 1588-2008 with above restrictions. When clocks are doubly attached, this profile extends the BMCA of IEC 61588:2009 ¦ IEEE Std 1588-2008 as IEC 62439-3:2016, Annex A, specifies. NOTE IEC 62439-3:2016, Annex B is identical to this part of IEC 61850, except that doubly attached clocks are mandatory, while this part of IEC 61850 leaves them optional.
Scope: This part of IEC 61850 specifies a precision time protocol (PTP) profile of IEC 61588:2009 ¦ IEEE Std 1588-2008 applicable to power utility automation, which allows compliance with the highest synchronization classes of IEC 61850-5 and IEC 61869-9.
Contents:
- FOREWORD
- INTRODUCTION
- Scope