High-voltage switchgear and controlgear – Part 303: Use and handling of sulphur hexafluoride (SF6)
Introduction: SF6 technology is used in switchgear and controlgear, for more than 30 years. Its application is mainly in electric power equipment for rated voltages exceeding 1 kV up to the highest rated voltages for which switchgear and controlgear are manufactured. It is estimated that several millions of the different types of SF6-filled units are currently in service. Three methods for gas containment are technically available, according to IEC 62271-1: controlled pressure system; NOTE 1 Controlled pressure systems are no longer used for new equipment, because of the unacceptable leakage rate (see IEC 62271-203). closed pressure system: modern high-voltage electric power equipments. The standardized values for leakage rates are 0,5 % and 1 % per year and per gas-filled compartment; sealed pressure system: modern medium-voltage electric power equipments (commercially designated as “sealed for life products” or “hermetically sealed systems”). The tightness of sealed pressure systems is specified by their expected operating life. The expected operating life with regard to leakage performance is specified by the manufacturer. Preferred values are 20, 30 and 40 years. NOTE 2 To fulfil the expected operating life requirement the leakage rate of the SF6 sealed pressure systems is considered to be less than 0,1 % per year. The long experience with the use of SF6 in switchgear and controlgear evidences that a certain number of elementary precautions and procedures should be adopted in order to
Scope: The scope of this technical report is to address the procedures for safe and environmental compatible handling of SF6 during installation, commissioning, normal and abnormal operations, disposal at the end-of-life of high-voltage switchgear and controlgear. Storage and transportation of SF6 are also covered. These procedures should be regarded as minimum requirements to ensure the safety of personnel working with SF6 and to minimize the SF6 emission to the environment. This technical report generally applies also to gas mixtures containing SF6. NOTE 1 For the use of this technical report, the term “ high voltage” (reference IEV 601-01-27) is the rated voltage above 1 000 V. However, the term “ medium voltage” (reference IEV 601-01-28) is commonly used for distribution systems with voltages above 1 kV and generally applied up to and including 52 kV. NOTE 2 Throughout this technical report, the term “electric power equipment” stands for “high-voltage and medium voltage switchgear and/or controlgear”.
Contents:
- FOREWORD
- INTRODUCTION
- Scope