FTIR analysis of fire effluents in cone calorimeter tests
Introduction: The composition of the effluent from an enclosure fire is determined by the combustible items in the enclosure, such as interior furnishings and wall linings, and the fire conditions within the enclosure. To represent any product involved in any fire scenario, the ideal fire test specimen is the complete item, and the ideal test is one conducted in an enclosure of appropriate size. Unfortunately, real-scale testing of commercial products is not generally economically feasible. This document describes an indicative approach for obtaining gas yields under specific fire conditions. It involves the use of a small-scale combustor in which a small test specimen is exposed to a pre-defined radiative heat flux. The test specimen should be representative of the finished product This document provides a method for continuous quantification of gases (i.e. time-resolved gas analysis) emitted from a test specimen exposed to irradiance in a cone calorimeter, after extraction of effluent gas to a FTIR gas analyser. It produces data as the gas volume fraction (µL/L) or gas yield (mg/ kg) during the test period. Data generated allow a better understanding of gas emissions during cone calorimeter tests, which can be useful for Fire Safety Engineering and for material development. Some examples of FTIR analysers used with cone calorimeters are presented in Table A.1. The cone calorimeter uses a well-ventilated physical fire model, so results are only relevant for this scenario. Toxicity assessm
Scope: This document specifies a method for determining the kinetics and yields of gaseous emissions from a specimen exposed to radiant heat in a cone calorimeter. Gas yields are determined by exposing small representative specimens to an external heat flux with or without spark ignition. The concentrations of specific gases in the effluent (smoke) are measured. In combination with calculated masses of gases, their yields from the specimen mass, mass loss or mass loss rate can be determined. This document uses Fourier-Transform Infrared (FTIR) spectroscopy as described in ISO 19702, with additional information on the test apparatus and gas analyser suitable for this specific application.